- Product description
-
Product descriptionV20 surge arrester, Type 2, for earthed photovoltaic systems
• Complete unit consisting of varistor arrester with cut-off unit
• For PV systems directly earthed on DC side to VDE 0100-712 (EN 50539-12)
• Surge protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• V20-C 3-PH-1000 tested to EN 50539-11 (VDE / KEMA)
• Arresting capacity to 40 kA (8/20) per pole
• Low DC voltage protection level: < 4.0 kV and Voc max = 1,000 V DC
• With visual function display for use in distributor housings
Application: Directly earthed PV systems with or without isolated lightning protection system
- Technical data
-
Technical data
Blow-out no Conductor cross-section, flexible (fine-wire), min. 25 mm² Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm² Conductor cross-section, rigid (single-wire/multiwire), min. 2,5 mm² DC network form yes Dimension 1000V DC Installation type DIN rail 35 mm Lightning protection zone LPZ 1→2 Max. mains-side overcurrent protection 125 Maximum back-up fuse 125 A Maximum continuous voltage DC 1000 V Maximum discharge current (8/20 μs) 40 kA Network form Other Nominal discharge current (8/20 µs) 20 kA Operating temperature, max. 80 °C Operating temperature, min. -40 °C Pole version 2 Protection rating IP20 Remote signalling no Response time <25 ns Signalling on device Visual SPD to EN 61643-11 Type 2 SPD to IEC 61643-1 Class II Test class, type 2 yes Version for 2-pole for earthed PV systems - All types
- Downloads
-
Data sheet V20-C 2-PH-1000 / 5094617 , 0.26MB , pdfCatalogue Überspannungsschutz , 28.42MB , pdfEU declaration of conformity V20-C 2-PH-1000 / 5094617 , 0.10MB , pdfLabel approval VDE test report V20-PH , 0.05MB , pdfLabel approval DEKRA test report V20-PH , 0.08MB , pdfSelection aid Selection aid, surge protection , 2.00MB , pdf
English