- Product description
-
Product descriptionFire protection duct made from water and frost-proof fibreglass light concrete of building material class A1 according to EN 13501-1 for fireproof laying of cables in rescue and emergency routes, and for the maintenance of electrical functionality of safety-relevant systems. Classification I90 as I duct according to DIN 4102 Part 11 and classification E30 as E duct according to DIN 4102 Part 12.
Mounting of the duct on wall brackets or as ceiling mounting with suspended supports and brackets or on a U transverse profile suspended with threaded rods. Mounted connectors ensure quick mounting in situ, whilst loosely placed covers ensure quick inspection and reassignment.
Fire protection duct with cover and pre-mounted connection fittings, connection crews and sealing strips.
- Technical data
-
Technical data
Colour Grey Cover fastening Loose Dimension 50x210 Dimension B 310 mm Dimension b 210 mm Dimension h 50 mm Dimension H 120 mm Fire resistance class E − function maintenance 30 Fire resistance class I − installation duct 90 Jacketing Without Length 1000 mm Material Fibreglass lightweight concrete Material of the insulation Glass-fibre lightweight concrete Number of flammable sides 4 Partitions possible yes With perforation no - All types
- Downloads
-
Data sheet BSKH 090521 / 7215182 , 0.20MB , pdfBrochure Brochure The Experts , 2.10MB , pdfCatalogue Brandschutzkanäle , 8.99MB , pdfEnvironmental declaration Umweltproduktdeklaration (EPD) , 1.48MB , pdfMounting instructions Mounting instructions, PYROLINE® Con BSK fire protection duct , 15.07MB , pdf